Does this exact PV topology fit every declared MPPT input limit?
Series adds module voltage; parallel strings add current. Correct Voc for the entered minimum cell temperature, then test absolute voltage, the operating window, short-circuit current and array power as separate gates.
Method
Cold module Voc applies the exact coefficient magnitude to the difference from 25°C. String Voc/Vmp multiply by modules in series; array Isc/Imp multiply by parallel strings; power multiplies Vmp, Imp and total module count.
Important limitation
An arithmetic pass cannot approve mixed modules, tracker allocation, shade, cable ampacity/drop, connectors, fusing, isolation, grounding, rapid shutdown, roof structure, battery charge settings or local code. Exact manuals and a qualified PV design control.